Types of Chiller Systems: Complete Guide
Chillers are refrigeration systems that remove heat from a process fluid — typically water or a water-glycol mixture — and reject it to the environment. There are several types of chiller systems, classified by condenser cooling method, compressor type, and application. This guide covers all major chiller types to help engineers and procurement teams select the right system for their project.
Get a Quote from Geson Chiller →
1. Classification by Condenser Type
Air Cooled Chillers
Air cooled chillers reject heat from the refrigerant directly to the outdoor air using condenser fans. No cooling tower or condenser water system is required.
- Capacity range: 3RT to 300RT (10kW to 1,050kW)
- Best for: Sites without water supply, smaller installations, outdoor mounting
- Advantages: Lower upfront cost, simpler installation, no cooling tower maintenance
- Disadvantages: Lower efficiency than water cooled, capacity drops in high ambient temperatures
Water Cooled Chillers
Water cooled chillers reject heat via a shell-and-tube condenser to a cooling water circuit, which carries heat to an external cooling tower. They are more efficient than air cooled chillers, particularly for large-capacity applications.
- Capacity range: 30RT to 4,500RT (105kW to 15,820kW)
- Best for: Large buildings, industrial plants, district cooling
- Advantages: Higher efficiency (COP 4.0–6.0), not affected by outdoor temperature
- Disadvantages: Requires cooling tower, condenser pump, and water treatment
| Factor | Air Cooled Chiller | Water Cooled Chiller |
|---|---|---|
| Typical COP | 2.5 – 3.5 | 4.0 – 6.0 |
| Capacity range | 3RT – 300RT | 30RT – 4,500RT |
| Cooling tower required | No | Yes |
| Installation complexity | Low | High |
| Upfront cost | Lower | Higher |
| Operating cost | Higher | Lower |
| Best for | Small/medium, no water supply | Large installations, continuous operation |
2. Classification by Compressor Type
Scroll Chillers
Scroll chillers use hermetic scroll compressors — typically two or more operating in tandem. They are quiet, reliable, and require minimal maintenance. Best suited for small to medium cooling loads with relatively stable demand.
- Capacity range: 3RT to 180RT
- Compressor brands: Copeland, Danfoss, Invotech, Daikin
- Best for: Food & beverage, injection molding, laser cooling, small HVAC
Screw Chillers
Screw chillers use twin-screw compressors with stepless capacity modulation via variable frequency drive (VFD). They deliver excellent part-load efficiency and are suited to applications with variable cooling demand.
- Capacity range: 50RT to 4,500RT
- Compressor brands: Hanbell, Bitzer, FUSHENG
- Best for: Industrial process cooling, large HVAC, data centers, district cooling
Centrifugal Chillers
Centrifugal chillers use a centrifugal compressor (impeller) and are designed for very large-scale cooling applications. They achieve the highest efficiency at full load and are the preferred choice for district cooling and large central plant.
- Capacity range: 300RT to 4,500RT+
- Best for: Hospitals, airports, district cooling, large hotels
| Compressor Type | Capacity Range | Part Load Efficiency | Best Application |
|---|---|---|---|
| Scroll | 3RT – 180RT | Good (step unloading) | Small/medium process cooling |
| Screw | 50RT – 4,500RT | Excellent (VFD stepless) | Industrial & large HVAC |
| Centrifugal | 300RT – 4,500RT+ | Best at full load | District cooling, large central plant |
3. Classification by Application
Process Chillers
Process chillers provide precise temperature control for industrial manufacturing processes. They operate at fixed setpoint temperatures, often below standard HVAC ranges, and must maintain stable temperature regardless of varying process loads.
- Temperature range: -45°C to +25°C
- Applications: Injection molding, pharmaceutical, chemical, food processing, laser cooling
HVAC Chillers
HVAC chillers provide chilled water for building air conditioning systems. They supply air handling units (AHUs) and fan coil units (FCUs) at standard chilled water temperatures of 6–12°C.
- Temperature range: 5°C to 15°C (standard chilled water)
- Applications: Office buildings, hotels, hospitals, shopping malls
Glycol Chillers
Glycol chillers use a water-glycol mixture as the secondary coolant, allowing operation below 0°C without freezing. Essential for food processing, brewing, ice rinks, and any application requiring sub-zero temperatures.
- Temperature range: -45°C to +10°C
- Applications: Brewing, food processing, ice rinks, pharmaceutical
Low Temperature Chillers
Low temperature chillers use cascade refrigeration systems to achieve outlet temperatures as low as -145°C. Used in pharmaceutical, chemical, and research applications requiring ultra-low temperatures.
- Temperature range: -145°C to -20°C
- Applications: Pharmaceutical R&D, chemical processing, cryogenic applications
4. How to Choose the Right Chiller Type
| Your Situation | Recommended Chiller Type |
|---|---|
| Small process cooling, no cooling tower | Air cooled scroll chiller (3–100RT) |
| Medium industrial process, no cooling tower | Air cooled screw chiller (50–300RT) |
| Large industrial process, cooling tower available | Water cooled screw chiller (50–4,500RT) |
| Sub-zero process temperature required | Glycol chiller or low temperature chiller |
| Building HVAC, central plant | Water cooled screw or centrifugal chiller |
| District cooling, 500RT+ | Water cooled centrifugal chiller |
| High ambient temperature (>43°C) | High-ambient air cooled chiller or water cooled |
Geson Chiller — All Types Available
Geson manufactures all major types of chiller systems from our factory in Nanjing, China. All units are CE and ISO 9001 certified, factory-tested before shipment, and shipped globally with 30-day lead time.
| Chiller Type | Capacity | Link |
|---|---|---|
| Water Cooled Screw & Scroll Chillers | 3RT – 4,500RT | View Product |
| Air Cooled Screw & Scroll Chillers | 3RT – 300RT | View Product |
| Glycol Refrigeration Systems | 3RT – 300RT | Learn More |
| Low Temperature Chillers | 3RT – 200RT | Enquire |
📧 info@gesonchiller.com
📱 WhatsApp: +86 138 5195 0629
GESON Industrial Chiller
- 50~400ton cooling capacity
- -5℃ chilled water temperature supply
- Loading adjusted 100%, 75%, 50%, 25%,0
- Branded screw compressors, simple structure, few breakdowns
500Tons Inverter Direct-drive Centrifugal Chiller
- Cooling capacity: 250~1300RT / 879~4571kW
- Refrigeration COP: 6.33~6.62
- Refrigeration IPLV: 8.10~9.07
- Energy Efficiency Level: Level 1